Will solar panels survive an EMP?
What was tested on the panels?
Sandia's report SAND2020-3824 (April 2020) covers radiated testing, October 10 to 17, 2019, of 8 PV modules exposed to E1 transient pulses at peak fields up to 100 kV/m. The modules were connected to a resistive load standing in for connected equipment. Curve tracing of each module's current and voltage showed no observable loss of device function. During the pulse, currents of tens of amps flowed through the module wiring for up to a microsecond, and common-mode currents reached peaks of tens to hundreds of amps. That is tested, for that panel type. It says little about other panel types, or about the equipment on the other end of the wires.
What about inverters and charge controllers?
An inverter turns the panels' direct current into household alternating current. A charge controller manages battery charging. Both contain electronics, and both are connected to long wires. Sandia also published "Effects of EMP Testing on Residential DC/AC Microinverters" (SAND2020-9847, September 2020). Its abstract says that EMP coupling can be destructive to components and that it applied high-voltage impulses meant to emulate EMP coupling to the AC and DC sides of small residential microinverters, with before and after measurements. The page we opened does not state the results, and we could not open the full report, so we do not report them here.
Charge controllers: we did not find a primary test.
Grid-tied versus off-grid
| Setup | Parts exposed | Evidence |
|---|---|---|
| Panels alone | Glass and cells, short leads | Tested (Sandia, 8 modules, up to 100 kV/m) |
| Grid-tied (inverter, utility connection) | Panels, inverter, house wiring, utility lines | Inverter result not confirmed by us. Also exposed to long utility and house wiring. |
| Off-grid (controller, battery, inverter) | Panels, controller, battery, inverter | Controller: unknown. Inverter: see above. |
How any particular inverter behaves in an outage or after a pulse is a question for its maker.
What EPRI said
The Electric Power Research Institute's 2019 summary of its study of high-altitude EMP says power plants, distribution systems and renewables were not covered and still need study. EPRI's findings on transmission relays do not say anything about household solar.
What we do not know
- Unknown: inverter and charge controller survival (no result we could confirm).
- Unknown: other panel types, such as thin-film, or whole mounted arrays with long wire runs.
- Unknown: the effect of E3, the slow pulse that drives current in very long power lines. Panel tests did not cover it.
- A solar storm is a different event and not the subject of the Sandia test.
What to do about it
- Treat the panels as the sturdy part, based on the Sandia result, and spend attention on the electronics.
- Ask the inverter and controller maker for any test report on pulse immunity. If they have none, treat it as unknown.
- If you add a spare controller or inverter, store it off and unconnected. This is expected to help, not tested.
- Have a licensed electrician do any work on your panel or wiring.
See also what to look for in backup power, generators and EMP and EMP versus solar storm.
Sources
- Sandia National Laboratories, High Altitude Electromagnetic Pulse Testing of Photovoltaic Modules, SAND2020-3824, April 2020. sandia.gov
- Sandia National Laboratories, Effects of EMP Testing on Residential DC/AC Microinverters, SAND2020-9847, September 2020 (abstract only). sandia.gov
- EPRI Journal, "A Deliberate Approach to Electromagnetic Pulses", 2019. eprijournal.com